Published August 2013 | Version v1
Journal article

Experimental evaluation of sodium to air heat exchanger performance

  • 1. Fast Reactor Technology Group, Indira Gandhi Centre for Atomic Research, Kalpakkam 603 102, Tamil Nadu (India)

Description

Highlights: ► Sodium to air heat exchangers are used to remove the decay heat produced in fast breeder reactor after shutdown. ► Finned tube sodium to air heat exchanger with sodium on tube side was tested for its heat transfer performance. ► A one dimensional computer code was validated by the experimental data obtained. ► Non uniform sodium and air flow distribution was present in the heat exchanger. - Abstract: Sodium to air heat exchangers (AHXs) is used in Prototype Fast Breeder Reactor (PFBR) circuits to reject the decay heat produced by the radioactive decay of the fission products after reactor shutdown, to the atmospheric air. The heat removal through sodium to air heat exchanger maintains the temperature of reactor components in the pool within safe limits in case of non availability of normal heat transport path. The performance of sodium to air heat exchanger is very critical to ensure high reliability of the decay heat removal systems in sodium cooled fast breeder reactors. Hence experimental evaluation of the adequacy of the heat transfer capability gives confidence to the designers. A finned tube cross flow sodium to air heat exchanger of 2 MW heat transfer capacity with sodium on tube side and air on shell side was tested in the Steam Generator Test Facility at Indira Gandhi Center for Atomic Research, India. Heat transfer experiments were carried out with forced circulation of sodium and air, which confirmed the adequacy of heat removal capacity of the heat exchanger. The testing showed that 2.34 MW of heat power is transferred from sodium to air at nominal flow and temperature conditions. A one dimensional computer code developed for design and analysis of the sodium to air heat exchanger was validated by the experimental data obtained. An equivalent Nusselt number, Nueq is derived by approximating that the resistance of heat transfer from sodium to air is contributed only by the film resistance of air. The variation of Nueq with respect to the Reynolds number was studied

Availability note (English)

Available from http://dx.doi.org/10.1016/j.anucene.2013.01.063

Additional details

Identifiers

DOI
10.1016/j.anucene.2013.01.063;
PII
S0306-4549(13)00090-X;

Publishing Information

Journal Title
Annals of Nuclear Energy (Oxford)
Journal Volume
58
Journal Page Range
p. 6-11
ISSN
0306-4549
CODEN
ANENDJ

Optional Information

Copyright
Copyright (c) 2013 Elsevier Science B.V., Amsterdam, The Netherlands, All rights reserved.