Published 1997 | Version v1
Miscellaneous

Characterization of electromagnetic noise at very high frequencies in Hydro-Quebec's 735 kV substations

  • 1. Institut de Recherche d'Hydro-Quebec, Varennes, PQ (Canada)

Description

Tests were conducted at a Hydro-Quebec 735 kV substation to characterize the electrical parameters of intrusive noise found at high frequencies (between 20 to 1000 MHz). A first series of measurements were made in 1991 and 1992 to determine the overall reliability of the remote digital protection system. Subsequent measurements were made in 1995 for a period of 7-1/2 months. Hundreds of records of intrusive noise were made. Circuit breaker opening and closing tests were repeatedly performed. Results showed that the intensity of the high-frequency intrusive electric fields in the substations was significantly greater than expected. These results will evidently impact on the specifications of immunity criteria and also on the future testing of telecommunications equipment. The frequency band and the severity levels required during standard tests were verified. 1 ref., 5 figs

Additional details

Publishing Information

Publisher
Institut de Recherche d'Hydro-Quebec
Imprint Place
Varennes, PQ (Canada)
Imprint Title
ISH '97: Conference Proceedings
Imprint Pagination
[CD-ROM]
Journal Page Range
p. 1-4

Conference

Title
10. international symposium on high voltage engineering
Dates
24-30 Aug 1997
Place
Montreal (Canada)

INIS

Country of Publication
Canada
Country of Input or Organization
Canada
INIS RN
29044788
Subject category
S24: POWER TRANSMISSION AND DISTRIBUTION; S42: ENGINEERING;
Resource subtype / Literary indicator
Conference, Non-conventional Literature
Descriptors DEI
ELECTROMAGNETIC FIELDS; EQUIPMENT PROTECTION DEVICES; INTERFERENCE; POWER SUBSTATIONS; RADIO NOISE
Descriptors DEC
ELECTROMAGNETIC RADIATION; NOISE; RADIATIONS; RADIOWAVE RADIATION

Optional Information

Notes
Imprint:6 v.
Secondary number(s)
CONF-970802--