Engineering analysis of electrical effects for the COTP 500KV transmission line and EBMUD aqueduct corridor

  • 1. East Bay Municipal Utility District, Oakland, CA (United States)
  • 2. SES Consulting, Inc., Sonoma, CA (United States)
  • 3. Safe Engineering Services, Montreal, Quebec (Canada)

Description

A study was conducted to determine AC electrical interference effects arising in the East Bay Municipal Utility District's (EBMUD) Mokelumne Aqueducts due to their proximity to the Olinda-Tracy 500 kilovolt (kV) transmission line operated by the Western Area Power Administration (WESTERN). A six-wire gradient control wire mitigation system selected by EBMUD was modeled and evaluated. The study shows that the mitigation system performs satisfactorily under all conditions examined. During steady state conditions, touch voltages are maintained below 15 volts throughout the entire length of the three aqueducts. During fault conditions, touch voltages are maintained below 263 volts, the design limit calculated according to ANSI/IEEE Standard 80. The currents flowing through the isolator/surge protectors do not exceed the ratings of these devices, during steady state and fault conditions

Additional details

Additional titles

Augmented title (English)
California Oregon Transmission Project

Publishing Information

Publisher
Institute of Electrical and Electronics Engineers, Inc.
Imprint Place
Piscataway, NJ (United States)
ISBN
0-7803-3008-0
Imprint Title
Conference record of the 1995 IEEE Industry Applications Society 30. IAS annual meeting. Volume 3
Imprint Pagination
961 p.
Journal Page Range
p. 2255-2262.
ISSN
0197-2618

Conference

Title
IEEE/Industrial Application Society conference.
Dates
8-12 Oct 1995.
Place
Orlando, FL (United States).

INIS

Country of Publication
United States
Country of Input or Organization
United States
INIS RN
28028086
Subject category
S24: POWER TRANSMISSION AND DISTRIBUTION;
Resource subtype / Literary indicator
Conference
Descriptors DEI
CALIFORNIA; ELECTRIC GROUNDS; ELECTRIC POTENTIAL; ELECTROMAGNETIC FIELDS; ENVIRONMENTAL EFFECTS; INTERCONNECTED POWER SYSTEMS; PIPES; POWER TRANSMISSION LINES
Descriptors DEC
DEVELOPED COUNTRIES; NORTH AMERICA; POWER SYSTEMS; USA

Optional Information

Secondary number(s)
CONF-9510203--.