Engineering analysis of electrical effects for the COTP 500KV transmission line and EBMUD aqueduct corridor
Creators
- 1. East Bay Municipal Utility District, Oakland, CA (United States)
- 2. SES Consulting, Inc., Sonoma, CA (United States)
- 3. Safe Engineering Services, Montreal, Quebec (Canada)
Description
A study was conducted to determine AC electrical interference effects arising in the East Bay Municipal Utility District's (EBMUD) Mokelumne Aqueducts due to their proximity to the Olinda-Tracy 500 kilovolt (kV) transmission line operated by the Western Area Power Administration (WESTERN). A six-wire gradient control wire mitigation system selected by EBMUD was modeled and evaluated. The study shows that the mitigation system performs satisfactorily under all conditions examined. During steady state conditions, touch voltages are maintained below 15 volts throughout the entire length of the three aqueducts. During fault conditions, touch voltages are maintained below 263 volts, the design limit calculated according to ANSI/IEEE Standard 80. The currents flowing through the isolator/surge protectors do not exceed the ratings of these devices, during steady state and fault conditions
Additional details
Additional titles
- Augmented title (English)
- California Oregon Transmission Project
Publishing Information
- Publisher
- Institute of Electrical and Electronics Engineers, Inc.
- Imprint Place
- Piscataway, NJ (United States)
- ISBN
- 0-7803-3008-0
- Imprint Title
- Conference record of the 1995 IEEE Industry Applications Society 30. IAS annual meeting. Volume 3
- Imprint Pagination
- 961 p.
- Journal Page Range
- p. 2255-2262.
- ISSN
- 0197-2618
Conference
- Title
- IEEE/Industrial Application Society conference.
- Dates
- 8-12 Oct 1995.
- Place
- Orlando, FL (United States).
INIS
- Country of Publication
- United States
- Country of Input or Organization
- United States
- INIS RN
- 28028086
- Subject category
- S24: POWER TRANSMISSION AND DISTRIBUTION;
- Resource subtype / Literary indicator
- Conference
- Descriptors DEI
- CALIFORNIA; ELECTRIC GROUNDS; ELECTRIC POTENTIAL; ELECTROMAGNETIC FIELDS; ENVIRONMENTAL EFFECTS; INTERCONNECTED POWER SYSTEMS; PIPES; POWER TRANSMISSION LINES
- Descriptors DEC
- DEVELOPED COUNTRIES; NORTH AMERICA; POWER SYSTEMS; USA
Optional Information
- Secondary number(s)
- CONF-9510203--.