Published 1984 | Version v1
Report

Decontamination of steam generators at Loviisa NPS - The decision making and the results

  • 1. Imatran Voima Oy, IMATRA Power Company, Radiation Protection Division, Loviisa (Finland)

Description

In 1980, during the annual inspections at Loviisa 1, 440 MWe PWR unit, some minor faults in the welding seams of the water chambers in two of the six steam generators were indicated. This led to enlarged inspection work and to thousands of working hours inside the steam generators. The plant had been three years in operation, so the dose rates in the steam generators were rather high. In this case it turned out, that a formal radiation protection optimization procedure would not give the answer on how to go ahead, as there were several practical and psychological factors influencing the decision making process. Anyhow, the result was that a decontamination apparatus was urgently planned and constructed, and advice on tested decontamination chemicals was received from the plant supplier. Using the decontamination machine with alternating basic and acid solutions, a decontamination factor of DF = 300 was reached, and the repair work could be performed without any restrictions on working time. This paper points out some limiting factors in the decision making process and describes the decontamination equipment, the decontamination solutions and the programme. The cost per saved collective dose unit is also calculated. (author)

Part of:
Radiation protection optimization 'as low as reasonably achievable',... Proceedings of the second European scientific seminar

Additional details

Publishing Information

ISBN
92-825-4499-0
Imprint Title
Radiation protection optimization 'as low as reasonably achievable',... Proceedings of the second European scientific seminar
Imprint Pagination
522 p.
Journal Page Range
p. 219-234
Report number
EUR--9173-EN

Conference

Title
2. European scientific seminar
Dates
8-9 Nov 1983
Place
Luxembourg (Luxembourg)

Optional Information

Notes
7 figs, 2 tabs