Published October 1991
| Version v1
Journal article
Field distribution on an HVDC wall bushing during laboratory rain tests
Creators
- 1. Swedish Transmission Research Inst., P.O. Box 707, 5-771 01 Ludvika (Sweden)
- 2. ABB Components, P.O. Box 706, S-771 01 Ludvika (Sweden)
Description
This paper reports that an efficient counter-measure to suppress flashovers across HVDC wall bushings is to make their surfaces hydrophobic. This laboratory investigation reports the measured electric field along such a bushing under different environmental conditions. A significantly reduced radial field strength has been found for the hydrophobic bushing. Moreover, the total field strength distribution becomes almost independent of the prevailing dry zone. The flashover voltage for bushings with a hydrophobic surface is therefore significantly increased
Additional details
Publishing Information
- Journal Title
- IEEE Transactions on Power Delivery
- Journal Volume
- 6
- Journal Issue
- 4
- Series
- IEEE Trans. Power Deliv.
- Journal Page Range
- 1531-1540
- ISSN
- 0885-8977
- CODEN
- ITPDE
INIS
- Country of Publication
- United States
- Country of Input or Organization
- United States
- INIS RN
- 23039439
- Subject category
- S24: POWER TRANSMISSION AND DISTRIBUTION;
- Descriptors DEI
- DESIGN; ELECTRICAL INSULATORS; ENVIRONMENTAL IMPACTS; FIELD TESTS; FLASHOVER; HVDC SYSTEMS; PLANNING; POWER DISTRIBUTION SYSTEMS; SAFETY
- Descriptors DEC
- DC SYSTEMS; ELECTRIC DISCHARGES; ELECTRICAL EQUIPMENT; EQUIPMENT; POWER SYSTEMS