Published October 1991 | Version v1
Journal article

Field distribution on an HVDC wall bushing during laboratory rain tests

  • 1. Swedish Transmission Research Inst., P.O. Box 707, 5-771 01 Ludvika (Sweden)
  • 2. ABB Components, P.O. Box 706, S-771 01 Ludvika (Sweden)

Description

This paper reports that an efficient counter-measure to suppress flashovers across HVDC wall bushings is to make their surfaces hydrophobic. This laboratory investigation reports the measured electric field along such a bushing under different environmental conditions. A significantly reduced radial field strength has been found for the hydrophobic bushing. Moreover, the total field strength distribution becomes almost independent of the prevailing dry zone. The flashover voltage for bushings with a hydrophobic surface is therefore significantly increased

Additional details

Publishing Information

Journal Title
IEEE Transactions on Power Delivery
Journal Volume
6
Journal Issue
4
Series
IEEE Trans. Power Deliv.
Journal Page Range
1531-1540
ISSN
0885-8977
CODEN
ITPDE

INIS

Country of Publication
United States
Country of Input or Organization
United States
INIS RN
23039439
Subject category
S24: POWER TRANSMISSION AND DISTRIBUTION;
Descriptors DEI
DESIGN; ELECTRICAL INSULATORS; ENVIRONMENTAL IMPACTS; FIELD TESTS; FLASHOVER; HVDC SYSTEMS; PLANNING; POWER DISTRIBUTION SYSTEMS; SAFETY
Descriptors DEC
DC SYSTEMS; ELECTRIC DISCHARGES; ELECTRICAL EQUIPMENT; EQUIPMENT; POWER SYSTEMS