The effects of design and operating factors on the frost growth and thermal performance of a flat plate fin-tube heat exchanger under the frosting condition

  • 1. Hanyang Univ., Seoul (Korea, Republic of)

Description

An experimental study of the effects of various factors(fin pitch, fin arrangement, air temperature, air humidity, and air velocity) on the frost growth and thermal performance of a fin-tube heat exchanger has been conducted under the frosting condition. It is found that the thermal performance of a heat exchanger is closely related to the blockage ratio of the air flow passages due to the frost growth. The maximum allowable blockage ratio is used to determine the criteria for the optimal operating conditions of a fin-tube heat exchanger. It is also shown that heat transfer rate of heat exchanger with staggered fin arrangement increases about 17% and the time required for heat transfer rate to reach a maximum value becomes longer, compared with those of an inline fin-tube heat exchanger under the frosting condition. The energy transfer resistance between the air and coolant decreases with the increase of inlet air temperature and velocity and with decreasing inlet air humidity

Additional details

Publishing Information

Journal Title
KSME International Journal
Journal Volume
13
Journal Issue
12
Series
10 refs, 12 figs, 3 tabs
Journal Page Range
p. 973-981
ISSN
1226-4865

INIS

Country of Publication
Korea, Republic of
Country of Input or Organization
Korea, Republic of
INIS RN
36106337
Subject category
S42: ENGINEERING;
Descriptors DEI
AIR FLOW; EVAPORATORS; FINS; FLOW BLOCKAGE; FROST; HEAT EXCHANGERS; HEAT TRANSFER; PERFORMANCE; TUBES
Descriptors DEC
ENERGY TRANSFER; FLUID FLOW; GAS FLOW; ICE