Design limitations for superconducting field magnet arrays on large hydrogenerators in the absence of shielding

Creators

  • 1. Imp Coll of Sci and Technol, London, Engl

Description

The electric design of an entirely new class of superconducting machines, i.e., the slow speed, multipolar hydrogenerator is described. Emphasis is on the design of field windings incorporating state-of-the-art Nb-Ti superconductor. The conceptual machine used to illustrate the limitations on the field array is a 60 Hz, 48 pole unit with a stator rating of 400 Mva; overall characteristics are compared with a conventional 615 Mva hydrogenerator. A specific superconducting cable shape is recommended for the field winding inductances, and inter-magnet attractive forces. A 230 kv stator winding is presented for investigating the large radial and attractive forces acting on the superconducting rotor as a function of load. 7 refs

Additional details

Publishing Information

Journal Title
IEEE Trans. Magn.
Journal Volume
MAG-15
Journal Issue
1
Series
IEEE Trans. Magn.
Journal Page Range
719-722