Published September 1975
| Version v1
Report
Meteorological effects of the mechanical-draft cooling towers of the Oak Ridge Gaseous Diffusion Plant
Creators
Description
The mechanical-draft cooling towers at the Oak Ridge Gaseous Diffusion Plant dissipate about 2000 MW of heat. Downwash occurs about 40 percent of the time, when wind speeds exceed about 3 m/sec. An elevated cloud forms about 10 percent of the time. The length of the visible plume, which is typically 100 or 200 m, is satisfactorily modeled if it is assumed that the plumes from all the cells in a cooling-tower bank combine. The calculation of fog concentration is complicated by the fact that the moisture is not inert but is taking part in the energy exchanges of a thermodynamic system. Calculations of drift deposition agree fairly well with observations
Additional details
Publishing Information
- Imprint Title
- 1974 annual report
- Imprint Pagination
- p. 55-70.
- Report number
- ATDL--75/17
INIS
- Country of Publication
- United States
- Country of Input or Organization
- United States
- INIS RN
- 7236663
- Subject category
- S58: GEOSCIENCES;
- Resource subtype / Literary indicator
- Progress Report
- Descriptors DEI
- ATMOSPHERIC PRECIPITATIONS; COOLING TOWERS; DIFFUSION; ENVIRONMENT; GASEOUS DIFFUSION PROCESS; GASEOUS WASTES; MATHEMATICAL MODELS; METEOROLOGY; ORGDP; PLUMES; SURFACE AIR; THERMAL EFFLUENTS; THERMODYNAMICS; TURBULENCE; VELOCITY; WASTE HEAT; WIND
- Descriptors DEC
- AIR; ENERGY SOURCES; FLUIDS; GASES; ISOTOPE SEPARATION; NATIONAL ORGANIZATIONS; SEPARATION PROCESSES; US ERDA; US ORGANIZATIONS; WASTES