This paper describes the results from aging, condition monitoring, and loss-of-coolant accident (LOCA) testing of class 1E electrical cables, per NUREG/CR-5772. This test was designed to test the performance of cables which had been aged with simultaneous radiation and thermal exposure. The tested cables included crosslinked polyolefin cables, ethylene propylene rubber cables, and miscellaneous cable types. Cables were exposed to 20, 40, and 60 years equivalent aging, and then exposed to LOCA tests at the end of their qualified life to determine the minimum insulation thickness needed for survival of the test. Failures were found in a large number of the tested cables. As a result the NRC has sent information notices to the industry regarding potential insulation problems. The results have raised the question of whether the artificial aging methods provide adequate testing methods. As a result of this testing the NRC is reviewing the artificial aging procedures, the adequacy of environmental qualification requirements for cable safety, and reexamining data from condition monitoring of installed cables

Files

Restricted

The record is publicly accessible, but files are restricted to users with access.

Part of:
International Atomic Energy Agency specialists meeting on experience in ageing, maintenance, and modernization of instrumentation and control systems for improving nuclear power plant availability

Additional details

Publishing Information

Imprint Title
International Atomic Energy Agency specialists meeting on experience in ageing, maintenance, and modernization of instrumentation and control systems for improving nuclear power availability
Imprint Pagination
577 p.
Journal Page Range
p. 69-87.
Report number
NUREG/CP--0134

Conference

Title
IAEA specialists meeting on experience in ageing, maintenance and modernization of instrumentation and control systems for improving nuclear power plant availability.
Dates
5-7 May 1993.
Place
Rockville, MD (United States).

Optional Information

Secondary number(s)