Emergency ac power systems operating experience at U.S. nuclear power plants - 1976 through 1983

Creators

  • 1. Oak Ridge National Laboratory, Oak Ridge, Tennessee (United States)

Description

Success and failure data of test and emergency starts of emergency ac power sources (diesel generators) at U.S. nuclear power plants were collected and evaluated to estimate diesel generator reliability parameters. A regression analysis of the estimates of the probability of failure to start based on surveillance test data from 1976 through 1983 indicates that the probability of failure to start has been decreasing. However, the reliability of diesel generator performance during losses of off-site power for 1981 through 1983 was less than expected based on the test data estimates. The failures that occurred during losses of off-site power were reviewed to determine why the calculated failure to start was greater than expected, and possible explanations for this high value are presented. The subsystems involved In diesel generator subsystem failures were categorized to determine whether there were any dominant failure modes. The results indicate that further significant Improvement in diesel generator reliability will require improvement of many subsystems. (author)

Files

47076515.pdf

Files (504.6 kB)

Name Size Download all
md5:11f1ba4af8e8e838217990e0d59ec32e
504.6 kB Preview Download
Part of:
Operating experience relating to on-site electric power sources. Proceedings of a Specialist Meeting

Additional details

Publishing Information

Imprint Title
Operating experience relating to on-site electric power sources. Proceedings of a Specialist Meeting
Imprint Pagination
399 p.
Journal Page Range
p. 30-40
Report number
NEA-CSNI-R--1986-115

Conference

Title
CSNI specialist meeting on operating experience relating to on-site electric power sources
Dates
16-18 Oct 1985
Place
London (United Kingdom)

Optional Information

Notes
6 refs.