Temperature control system for liquid-fed ceramic melters
Description
A temperature-feedback system has been developed for controlling electrical power to liquid-fed ceramic melters (LFCM). Software, written for a microcomputer-based data acquisition and process monitoring system, compares glass temperatures with a temperature setpoint and adjusts the electrical power accordingly. Included in the control algorithm are steps to reject failed thermocouples, spatially average the glass temperatures, smooth the averaged temperatures over time using a digital filter, and detect foaming in the glass. The temperature control system has proved effective during all phases of melter operation including startup, steady operation, loss of feed, and shutdown. This system replaces current, power, and resistance feedback control systems used previously in controlling the LFCM process
Availability note (English)
MF available from INIS under the Report Number; Available from NTIS, PC A03/MF A01; 1 as DE87002135.
Files
Additional details
Publishing Information
- Imprint Pagination
- 33 p.
- Report number
- PNL--6009
INIS
- Country of Publication
- United States
- Country of Input or Organization
- United States
- INIS RN
- 18052913
- Subject category
- S12: MANAGEMENT OF RADIOACTIVE WASTES, AND NON-RADIOACTIVE WASTES FROM NUCLEAR FACILITIES;
- Descriptors DEI
- CERAMIC MELTERS; CONTROL SYSTEMS; ELECTRIC POWER; HIGH-LEVEL RADIOACTIVE WASTES; RADIOACTIVE WASTE PROCESSING; VITRIFICATION
- Descriptors DEC
- ELECTRIC FURNACES; FURNACES; MANAGEMENT; MATERIALS; POWER; RADIOACTIVE MATERIALS; RADIOACTIVE WASTES; WASTE MANAGEMENT; WASTE PROCESSING; WASTES
Optional Information
- Notes
- Portions of this document are illegible in microfiche products. Original copy available until stock is exhausted.