NRC Information No. 87-24: Operational experience involving losses of electrical inverters

Creators

  • 1. Nuclear Regulatory Commission, Washington, DC (United States). Office of Nuclear Reactor Regulation

Description

The NRC case study report identified three potential failure mechanisms for inverters. One of these involves relatively high ambient temperature and/or humidity within inverter enclosures. This condition appears to result in accelerated aging of components that form a part of the inverter circuitry causing a significant reduction in component life expectancy and inverter loss. Another mechanism for inverter failure involves the electrical interconnecting and physical arrangements for the inverter circuitry components. In some installations, these arrangements are such that when certain components fail, other components also may fail or degrade. The third failure mechanism involves voltage spikes and perturbations. Many of the electrical loads in a plant have inductive characteristics. During plant operations that involve energizing and deenergizing these loads, voltage spikes and perturbations are generated. The solid-state devices in the inverter circuitry are sensitive to these voltage spikes, and this has resulted in component failure, blown fuses, and inverter losses. Additionally, secondary voltage perturbations caused by lighting strikes or switching surges can have an adverse effect on inverter operation

Part of:
Nuclear EQ sourcebook: A compilation of documents for nuclear equipment qualification

Additional details

Publishing Information

Publisher
IEEE Standards Press.
Imprint Place
Piscataway, NJ (United States)
ISBN
1-55937-206-0
Imprint Title
Nuclear EQ sourcebook: A compilation of documents for nuclear equipment qualification
Imprint Pagination
1360 p.
Journal Page Range
p. 3, Paper 71.

Optional Information