Measurement of steam temperature fluctuations at outlet of once through steam generator tubes

  • 1. Indira Gandhi Centre for Atomic Research, Kalpakkam (India)

Description

The 40 MW(t) Fast Breeder Test Reactor at Kalpakkam has two once through steam generator modules operating in parallel in each of its two secondary sodium loops. Temperature fluctuations at tube outlet were measured at different power levels up to 10.1 MW(t) using 1 mm diameter grounded junction thermocouples. At 8.8 MW(t), due to low superheat, random fluctuations in temperature with amplitude up to 5 deg.C were observed in some tubes. By analysing the statistical features of the temperature signal, it was concluded that these fluctuations are not indicative of any instability in the steam generator. (authors)

Part of:
SMORN VII. V.1

Additional details

Additional titles

Original title (English)
Mesure des fluctuations de temperature de la vapeur en sortie de tubes de generateurs de vapeur a passage direct

Publishing Information

Publisher
Organisation for Economic Co-Operation and Development.
Imprint Place
Paris (France)
Imprint Title
SMORN VII. V.1
Imprint Pagination
598 p.
Journal Page Range
p. 256-263.

Conference

Title
Symposium on nuclear reactor surveillance and diagnostics.
Dates
19-23 Jun 1995.
Place
Avignon (France).

Optional Information