Published March 2006
| Version v1
Journal article
The impact of photovoltaic systems on distribution transformer: A case study
- 1. IIE, Non-Conventional Energy Sources Department, P.O. Box 1-475, Cuernavaca, Morelos 62091 (Mexico)
- 2. Cenidet, Electronics Department, P.O. Box 5-164, Cuernavaca, Morelos 62050 (Mexico)
Description
In this paper, the results obtained after monitoring a distribution transformer during an 18 months period are described and discussed. The transformer fed several households, each with a grid connected photovoltaic system, and it was found that the power factor at the transformer attained unusually low levels. This was due to the fact that under some conditions, the systems provided a large portion of the active power demanded by the households, while the grid supplied all the reactive and distortion powers. The operating temperature was used as an indicator of the stress on the transformer. The temperature was at its lowest when the systems were providing the maximum energy available from the solar cells
Additional details
Identifiers
- DOI
- 10.1016/j.enconman.2005.04.007;
- PII
- S0196-8904(05)00104-4;
Publishing Information
- Journal Title
- Energy Conversion and Management
- Journal Volume
- 47
- Journal Issue
- 4
- Journal Page Range
- p. 311-321
- ISSN
- 0196-8904
- CODEN
- ECMADL
INIS
- Country of Publication
- United Kingdom
- Country of Input or Organization
- International Atomic Energy Agency (IAEA)
- INIS RN
- 37069309
- Subject category
- S14: SOLAR ENERGY;
- Descriptors DEI
- HOUSEHOLDS; MONITORING; POWER DEMAND; POWER DISTRIBUTION; POWER FACTOR; SOLAR CELLS; TRANSFORMERS
- Descriptors DEC
- DEMAND; DIMENSIONLESS NUMBERS; DIRECT ENERGY CONVERTERS; ELECTRICAL EQUIPMENT; EQUIPMENT; PHOTOELECTRIC CELLS; PHOTOVOLTAIC CELLS; SOLAR EQUIPMENT
Optional Information
- Copyright
- Copyright (c) 2005 Elsevier Science B.V., Amsterdam, The Netherlands, All rights reserved.