Published March 2018 | Version v1
Journal article

Experimental assessment of double-absorption heat transformer operating with H2O/LiBr

  • 1. Instituto de Energías Renovables, Universidad Nacional Autónoma de México, Temixco, Morelos (Mexico)
  • 2. Centro de Ingeniería y Ciencias Aplicadas, Universidad Autónoma del Estado de Morelos, Av. Universidad 1001, C.P. 62209 Cuernavaca, Morelos (Mexico)

Description

Highlights: • A double-absorption heat transformer was developed operating with H2O/LiBr. • Gross temperature lifts as high as 74 °C were achieved with the system. • The gross temperature lifts are the highest reported in the literature using H2O/LiBr. • Up to 37% of the energy supplied to the DAHT could be retrieved at higher temperature levels. - Abstract: This paper reports on the experimental results of a double-absorption heat transformer operating with a H2O/LiBr mixture. The generator and evaporator are pool boiling type heat exchangers, while the remaining components are coils inside shells. Plots of gross temperature lifts, economizer efficiency, and internal and external performance coefficients are reported as functions of diverse operating parameters of the heat transformer. The results indicate that the system can achieve gross temperature lifts (GTLs) of between 48 °C and 74 °C, with internal performance coefficients varying from 0.12 to 0.37. The GTLs achieved are up to 30 °C higher than those reported in the literature, using a single-stage heat transformer operating with the same working mixture. Furthermore, the system exhibits effective stability and repeatability.

Availability note (English)

Available from http://dx.doi.org/10.1016/j.applthermaleng.2017.12.117

Additional details

Identifiers

DOI
10.1016/j.applthermaleng.2017.12.117;
PII
S1359431117349906;

Publishing Information

Journal Title
Applied Thermal Engineering
Journal Volume
132
Journal Page Range
p. 432-440
ISSN
1359-4311
CODEN
ATENFT

Optional Information

Notes
© 2017 Elsevier Ltd. All rights reserved.