Seismic and tsunami safety margin assessment
Description
Nuclear Regulation Authority is going to establish new seismic and tsunami safety guidelines to increase the safety of NPPs. The main purpose of this research is testing structures/components important to safety and tsunami resistant structures/components, and evaluating the capacity of them against earthquake and tsunami. Those capacity data will be utilized for the seismic and tsunami back-fit review based on the new seismic and tsunami safety guidelines. The summary of the program in 2012 is as follows. 1. Component seismic capacity test and quantitative seismic capacity evaluation. PWR emergency diesel generator partial-model seismic capacity tests have been conducted and quantitative seismic capacities have been evaluated. 2. Seismic capacity evaluation of switching-station electric equipment. Existing seismic test data investigation, specification survey and seismic response analyses have been conducted. 3. Tsunami capacity evaluation of anti-inundation measure facilities. Tsunami pressure test have been conducted utilizing a small breakwater model and evaluated basic characteristics of tsunami pressure against seawall structure. (author)
Additional details
Publishing Information
- Imprint Title
- Annual safety research report, JFY 2012
- Imprint Pagination
- 708 p.
- Journal Page Range
- p. 131-140
- Report number
- JNES-RE--2013-0001-Rev.1
INIS
- Country of Publication
- Japan
- Country of Input or Organization
- Japan
- INIS RN
- 51066967
- Subject category
- S22: GENERAL STUDIES OF NUCLEAR REACTORS;
- Resource subtype / Literary indicator
- Non-conventional Literature
- Descriptors DEI
- DIESEL ENGINES; ELECTRIC GENERATORS; EVALUATION; NUCLEAR POWER PLANTS; PERFORMANCE TESTING; POWER SUPPLIES; PWR TYPE REACTORS; SEAWATER; SEISMIC EFFECTS; WALLS
- Descriptors DEC
- ELECTRICAL EQUIPMENT; ELECTRONIC EQUIPMENT; ENGINES; ENRICHED URANIUM REACTORS; EQUIPMENT; HEAT ENGINES; HYDROGEN COMPOUNDS; INTERNAL COMBUSTION ENGINES; NUCLEAR FACILITIES; OXYGEN COMPOUNDS; POWER PLANTS; POWER REACTORS; REACTORS; TESTING; THERMAL POWER PLANTS; THERMAL REACTORS; WATER; WATER COOLED REACTORS; WATER MODERATED REACTORS
Optional Information
- Notes
- 3 refs., 17 figs., 4 tabs.; This record replaces 46066579