Published August 2016 | Version v1
Miscellaneous Open

Repair a chiller pump P 62303 to support radioactive waste installation

  • 1. Pusat Teknologi Limbah Radioaktif (PTLR) - BATAN, Kawasan Puspiptek Serpong, Tangerang Selatan 15314 (Indonesia)

Description

Repair chiller pump for indications of cooling water droplets on the seal pump is air-wasters. In the visual observation of the seal cooling water droplets above the range of 15 drops per minute, for normal conditions is permitted droplets: 10 sid 15 drop per minute. Because beyond normal limits then need immediate replacement, among others: gland packing, gland follower as it broke, shaft sleeve for wear, and rubber clutch. After the replacement chiller pump P 62303 test functions and adjustment. The result obtained by the cooling water droplets are 11 drops per minute, so that the pump can operate properly. (author)

Files

50001814.pdf

Files (2.2 MB)

Name Size Download all
md5:56c37ff0f611312209ee2803ecf9108b
2.2 MB Preview Download
Part of:
Proceeding of the 2015 research results and activities of radioactive waste technology center

Additional details

Additional titles

Original title (Indonesian)
Perbaikan pompa chiller P 62303 sebagai penunjang instalasi pengolahan limbah radioaktif

Publishing Information

Publisher
Center for Radioactive Waste Technology, National Nuclear Energy Agency
Imprint Place
Tangerang Selatan (Indonesia)
Imprint Title
Proceeding of the 2015 research results and activities of radioactive waste technology center
Imprint Pagination
[307 p.]
Journal Page Range
p. 181-186
ISSN
0852-2979
Report number
INIS-ID--79

Conference

Title
Research results and activities of radioactive waste technology center
Original Conference Title
Hasil penelitian dan kegiatan pusat teknologi limbah radioaktif
Dates
25-26 Apr 2015
Place
Tangerang Selatan (Indonesia)

INIS

Country of Publication
Indonesia
Country of Input or Organization
Indonesia
INIS RN
50001814
Subject category
S22: GENERAL STUDIES OF NUCLEAR REACTORS;
Resource subtype / Literary indicator
Conference
Descriptors DEI
COOLING; COOLING SYSTEMS; DROPLETS; ERRORS; PUMPS; REPAIR
Descriptors DEC
ENERGY SYSTEMS; EQUIPMENT; PARTICLES

Optional Information

Notes
5 refs.; 2 tabs.; 4 figs. Imprint:Prosiding hasil penelitian dan kegiatan pusat teknologi limbah radioaktif tahun 2015