Published 1981 | Version v1
Miscellaneous Open

Behaviour of the steam generators in the Belgian nuclear power plants

  • 1. Laboratoire Belge de l'Industrie Electrique (LABORELEC), Linkebeek (Belgium)

Description

After a brief review of the degradations occurring on tubes of Inconel 600 in steam generators of PWR power stations emphasis is put on the conditioning of the secondary water and more particularly on the condensate treatment in the units of Doel which work on heavily polluted brackish water. The important role of non-destructive testing and eddy-current testing is also pointed out, method developed by Laborelec. The operational experience shows that Belgian stations are nearly not concerned by the degradations mostly found in power stations in other countries which shows the efficiency of the conditioning of the secondary water. On the other hand, other problems have occurred, resulting from: damage caused by foreign objects; fouling of tube before commissioning, cracking of bends and at the limit of the dudgeoning and leaking plugs. (AF)

Availability note (English)

MF available from INIS under the Report Number.

Files

13708843.pdf

Files (416.5 kB)

Name Size Download all
md5:bc0534485f4fbed2da1cd495bd657ab9
416.5 kB Preview Download

Additional details

Additional titles

Original title (French)
Comportement des generateurs de vapeur des centrales nucleaires belges

Publishing Information

Imprint Pagination
11 p.
Report number
INIS-mf--7350

Conference

Title
International study meeting on modern power stations.
Dates
26 - 30 Oct 1981.
Place
Liege, Belgium.

Optional Information

Notes
23 refs.