Published June 1998 | Version v1
Report Open

Quadratic controller syntheses for the steam generator water level

Description

The steam generator water level, (SGWL), control problem in the pressurized water reactor of a nuclear power plant is considered from robust control techniques point of view. The plant is a time-varying system with a non minimum phase behavior and an unstable open-loop response. The time-varying nature of the plant due to change in operating power is taken into account by including slowly time-varying uncertainty in the model. A linear Time-Invariant, (LTI) guaranteed cost quadratic stabilizing controller is designed in order to address some of the particular issues arising for such a control problem. (author)

Availability note (English)

Available from INIS in electronic form

Files

30040914.pdf

Files (310.0 kB)

Name Size Download all
md5:696ccccdcf5250e89108326a8394c3eb
310.0 kB Preview Download

Additional details

Publishing Information

Imprint Pagination
16 p.
Report number
CNRS-R--98266

Optional Information

Notes
17 refs.