Published August 1997 | Version v1
Report

In-place HEPA filter penetration test

  • 1. Lawrence Livermore National Lab., CA (United States)

Description

We have demonstrated the feasibility of conducting penetration tests on high efficiency particulate air (HEPA) filters as installed in nuclear ventilation systems. The in-place penetration test, which is designed to yield equivalent penetration measurements as the standard DOP efficiency test, is based on measuring the aerosol penetration of the filter installation as a function of particle size using a portable laser particle counter. This in-place penetration test is compared to the current in-place leak test using light scattering photometers for single HEPA filter installations and for HEPA filter plenums using the shroud method. Test results show the in-place penetration test is more sensitive than the in-place leak test, has a similar operating procedure, but takes longer to conduct. Additional tests are required to confirm that the in-place penetration test yields identical results as the standard dioctyl phthalate (DOP) penetration test for HEPA filters with controlled leaks in the filter and gasket and duct by-pass leaks. Further development of the procedure is also required to reduce the test time before the in-place penetration test is practical. 14 refs., 14 figs., 3 tabs

Additional details

Publishing Information

Imprint Title
Proceedings of the 24. DOE/NRC nuclear air cleaning and treatment conference
Imprint Pagination
1022 p.
Journal Page Range
p. 649-670
Report number
NUREG-CP--0153

Conference

Title
24. nuclear air cleaning and treatment conference
Dates
15-18 Jul 1996
Place
Portland, OR (United States)

Optional Information

Secondary number(s)
CONF-960715--