Published 1989 | Version v1
Miscellaneous

Improving reliability of the uninterruptible power supply (UPS) inverters at Point Lepreau

  • 1. New Brunswick Electric Power Commission, Fredericton, NB (Canada)

Description

In nuclear generating plants inverters are required to provide clean uninterruptible AC power to critical loads such as safety systems, computers and process control. Upon inverter failure, many systems are designed to have a static switch transfer the load, in a no-break manner, to a regulated bypass supply. Failure of the transfer can greatly increase the risk of a plant trip. Recent failures of both the inverter and transfer equipment warranted a review of system design and maintenance practices. The review findings indicated that, due to age related degradation, a number of the inverter critical components were not functioning properly. this resulted in the 'violent' failure of solid state components within the inverter. Resultant transfers to the bypass supply were not successful because noise induced spurious operation of logic permissives at that critical time. In order to increase the system reliability, the inverter components and transfer logic has been upgraded along with an improved maintenance program. (author). 3 figs

Part of:
Proceedings of the 29th annual conference of the Canadian Nuclear Association and 10th annual conference of the Canadian Nuclear Society. V. 1-3

Additional details

Publishing Information

ISBN
0-919307-39-6; 0-919784-17-8
Imprint Title
Proceedings of the 29th annual conference of the Canadian Nuclear Association and 10th annual conference of the Canadian Nuclear Society. V. 1-3
Imprint Pagination
3 v. [1200 p.].
Journal Page Range
v. 3 p. 16.15-16.19.
ISSN
0706-1293; 0227-1907