An experimental study on fire rated cables for the exemption from cable separation requirements
- 1. FILK, Ryeoju (Korea, Republic of)
- 2. KEPRI, Taejon (Korea, Republic of)
Description
I stated on the fire resistibility of cables for providing fire shutdown capability in nuclear power plant at the Korean Nuclear Society FY '01 Spring Meeting. During the meeting, I was asked if cables' integrity could be maintained under condition that water spray was applying at cables and cable trays were escaped from its position by flame. In accordance with this question, we analyzed the result of tests which is described in IEC 60331 and BS 6387. As one of methods for implementation to conform to separation requirements in nuclear power plant, we reviewed the fire wrapping method by fire barrier having a 1-hour fire resistance rating. However, it costs too much to wrap cables. Therefore, we had tried to find out alterntive to minimize fire wrapping. As a result, we have obtained test results on using fire resistance cable (i.e. NFR-8) which is an affirmative substitution instead of fire wrapping
Additional details
Publishing Information
- Publisher
- KNS
- Imprint Place
- Taejon (Korea, Republic of)
- Imprint Title
- Proceedings of the Korean Nuclear Society autumn meeting
- Imprint Pagination
- [CD-ROM]
- Journal Page Range
- [9 p.]
Conference
- Title
- 2001 autumn meeting of the Korean Nuclear Society
- Dates
- 24-26 Oct 2001
- Place
- Seoul (Korea, Republic of)
INIS
- Country of Publication
- Korea, Republic of
- Country of Input or Organization
- Korea, Republic of
- INIS RN
- 33065425
- Subject category
- S42: ENGINEERING; S22: GENERAL STUDIES OF NUCLEAR REACTORS;
- Resource subtype / Literary indicator
- Conference, Non-conventional Literature
- Descriptors DEI
- ELECTRIC CABLES; FIRES; FLAMMABILITY; NUCLEAR POWER PLANTS; REACTOR CONTROL SYSTEMS; REACTOR SAFETY; REACTOR SHUTDOWN
- Descriptors DEC
- CABLES; COMBUSTION PROPERTIES; CONDUCTOR DEVICES; CONTROL SYSTEMS; ELECTRICAL EQUIPMENT; EQUIPMENT; NUCLEAR FACILITIES; POWER PLANTS; SAFETY; SHUTDOWN; THERMAL POWER PLANTS
Optional Information
- Notes
- 11 refs, 9 figs, 2 tabs