Published October 2015 | Version v1
Journal article

RCCS Operation with a Resonant Frequency Error in the KOMAC

  • 1. Korea Atomic Energy Research Institute, Gyeongju (Korea, Republic of)

Description

The resonance control cooling systems (RCCSs) of the Korea Multi-purpose Accelerator Complex have been operated for cooling the drift tubes (DT) and controlling the resonant frequency of the drift tube linac (DTL). The DTL should maintain a resonant frequency of 350 MHz during operation. A RCCS can control the temperature of the cooling water to within ±0.1 ◦C by using a 3-way valve opening and has a constant-cooling-water-temperature control mode and resonant-frequency-control mode. In the case of the resonant-frequency control, the error in the frequency is measured by using the low-level radio-frequency control system, and the RCCS uses a proportional-integral-derivative control algorithm to compensate for the error by controlling the temperature of the cooling water to the DT.

Additional details

Publishing Information

Journal Title
Journal of the Korean Physical Society
Journal Volume
67
Journal Issue
8
Series
3 refs, 15 figs
Journal Page Range
p. 1402-1405
ISSN
0374-4884

INIS

Country of Publication
Korea, Republic of
Country of Input or Organization
Korea, Republic of
INIS RN
49069667
Subject category
S43: PARTICLE ACCELERATORS;
Descriptors DEI
ACCELERATORS; ALGORITHMS; CONTROL SYSTEMS; COOLING SYSTEMS; DRIFT TUBES; ERRORS; MAINTENANCE
Descriptors DEC
ENERGY SYSTEMS; MATHEMATICAL LOGIC