There is a newer version of the record available.

Published January 2020 | Version v1
Journal article

Research on cold helium automatic cooling scheme of 650 MHz double-cell superconducting cavity

  • 1. Institute of High Energy Physics, Chinese Academy of Sciences, Beijing (China)

Description

In this paper, the cooling process of the 650 MHz double-cell superconducting cavity in Platform of Advanced Photon Source Technology R and D (PAPS) was taken as the main research object. The integral heat transfer model was constructed by using the criterion relation method and computational fluid dynamics (CFD) method, and the pre-inlet parameters of cold helium for superconducting cavity in the cooling process were obtained by programming calculation. According to the back-stepping process of the pre-inlet parameters, the relation between the opening percent of the temperature-changing valve and the pre-inlet parameters was calculated with full consideration of the overall layout and local resistance loss. The automatic control of the whole cooling process can be realized by the timetable of the opening percent of the temperature-changing valve. (authors)

Additional details

Publishing Information

Journal Title
Atomic Energy Science and Technology
Journal Volume
54
Journal Issue
1
Journal Page Range
p. 179-186
ISSN
1000-6931

Optional Information

Notes
9 figs., 16 refs.; http://dx.doi.org/10.7538/yzk.2019.youxian.0066