Published October 1990 | Version v1
Journal article

Guidelines for estimation of cabinet dynamic amplification

  • 1. Anco Engineers, Inc., Culver City, CA (USA)

Description

The use of GERS (generic equipment ruggedness spectra) for screening purposes in plant relay evaluations requires the comparison of relay GERS to mounting point response spectra. At best, only rough estimates of floor spectra (base input to an enclosure or panel0 are available. Since at the outset of a relay evaluation the specific location of a given relay is, in general, unknown, a simple approximate method of estimating the mounting point response is desirable. Based upon review of test data and judgmental evaluation of narrow- and broad-band response comparison, conservative single value amplification factors are recommended. Examples of MCC (Motor Control Center) and flexible panel screening amplification factors are presented. Screening amplification factors of 3.0 and 6.0 for MCC and flexible panels, respectively, are recommended for use in relay evaluations. (orig.)

Additional details

Publishing Information

Journal Title
Nuclear Engineering and Design
Journal Volume
123
Journal Issue
2/3
Series
Nucl. Eng. Des.
Journal Page Range
247-255
ISSN
0029-5493
CODEN
NEDEA

Conference

Title
2. symposium on current issues related to nuclear power plant structures, equipment and piping.
Dates
7-9 Dec 1988.
Place
Orlando, FL (USA).

INIS

Country of Publication
Netherlands
Country of Input or Organization
Netherlands
INIS RN
22023268
Subject category
S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS; S58: GEOSCIENCES;
Resource subtype / Literary indicator
Conference
Descriptors DEI
EARTHQUAKES; ELECTRIC MOTORS; NUCLEAR POWER PLANTS; REACTOR COMPONENTS; RELAYS; RESPONSE FUNCTIONS; SEISMIC EFFECTS; SOIL-STRUCTURE INTERACTIONS
Descriptors DEC
ELECTRICAL EQUIPMENT; EQUIPMENT; FUNCTIONS; MOTORS; NUCLEAR FACILITIES; POWER PLANTS; THERMAL POWER PLANTS