Published 1996 | Version v1
Book

Retrofit of existing buildings

  • 1. Parsons Power, Reading, PA (United States)

Description

A linear dynamic analysis procedure was used to evaluate the safety margin of an aged steel building in a Department of Energy plant against natural phenomena hazards such as winds, floods and earthquakes. This is a common industry practice and it is generally justifiable. It was shown that the use of this conventional procedure over-estimated the structural response and, subsequently, resulted in cost-prohibitive modification schemes. An alternate procedure was developed to provide realistic results and to minimize modification cost. A three-dimensional finite element model of the subject building was developed to analyze the different load combinations. Analysis results revealed deficiencies in the existing vertical bracing system used to resist lateral loads. The vertical bracing consisted of single-angle X bracing. An external bracing system was designed in a manner that would not impact the operation of the 56,000 square foot facility which has been processing fuel for power generating plants since 1954

Additional details

Publishing Information

Publisher
American Power Conference.
Imprint Place
Chicago, IL (United States)
Imprint Title
Proceedings of the American Power Conference. Volume 58-I
Imprint Pagination
767 p.
Journal Page Range
p. 466-472.
ISSN
0097-2126

Conference

Title
58. annual meeting of the American power conference.
Dates
9-11 Apr 1996.
Place
Chicago, IL (United States).

INIS

Country of Publication
United States
Country of Input or Organization
United States
INIS RN
28001703
Subject category
S22: GENERAL STUDIES OF NUCLEAR REACTORS;
Resource subtype / Literary indicator
Conference
Descriptors DEI
DYNAMIC LOADS; FINITE ELEMENT METHOD; FUEL FABRICATION PLANTS; MATHEMATICAL MODELS; SAFETY ANALYSIS
Descriptors DEC
CALCULATION METHODS; NUCLEAR FACILITIES; NUMERICAL SOLUTION

Optional Information

Secondary number(s)
CONF-960426--.