Published February 1997 | Version v1
Report Restricted

Steam generators secondary side chemical cleaning at Point Lepreau using the Siemens high temperature process

  • 1. New Brunswick Power Corp., Lepreau (Canada)
  • 2. Siemens AG, Erlangen (Germany)

Description

This paper describes the chemical cleaning of the four steam generators at the Point Lepreau facility, which was accomplished as a part of a normal service outage. The steam generators had been in service for twelve years. Sludge samples showed the main elements were Fe, P and Na, with minor amounts of Ca, Mg, Mn, Cr, Zn, Cl, Cu, Ni, Ti, Si, and Pb, 90% in the form of Magnetite, substantial phosphate, and trace amounts of silicates. The steam generators were experiencing partial blockage of broached holes in the TSPs, and corrosion on tube ODs in the form of pitting and wastage. In addition heat transfer was clearly deteriorating. More than 1000 kg of magnetite and 124 kg of salts were removed from the four steam generators

Files

Restricted

The record is publicly accessible, but files are restricted to users with access.

Additional details

Publishing Information

Imprint Title
Proceedings of the CNRA/CSNI workshop on steam generator tube integrity in nuclear power plants
Imprint Pagination
621 p.
Journal Page Range
p. 471-484.
Report number
NUREG/CP--0154

Conference

Title
CNRA/CSNI workshop on steam generator tube integrity in nuclear power plants.
Dates
30 Oct - 2 Nov 1995.
Place
Oak Brook, IL (United States).

Optional Information