Published March 2007 | Version v1
Journal article

Tolerant control for multiple faults of sensors in VAV systems

  • 1. School of Mechanical Engineering, Shanghai Jiao Tong University, Shanghai 200030 (China)

Description

Principal component analysis, joint angle plots and reconstruction schemes are presented in this paper to detect, isolate and evaluate multiple sensors faults occurring in variable air volume (VAV) systems. Multi-level principal component analysis models, including system level and local level, are built to detect multiple faults occurring in VAV systems. As the initial detection, a system level model is used to discover the abnormalities in view of the whole systems. Two local level models are used to further confirm the occurrence of the faults. Moreover, with the multiple faults separated into different locations by the two local level detection models, joint angle plots are used, respectively, to isolate the faults one by one. Finally, the reconstruction scheme is used to estimate the magnitude of the bias to recover from the faulty operation

Additional details

Identifiers

DOI
10.1016/j.enconman.2006.09.007;
PII
S0196-8904(06)00287-1;

Publishing Information

Journal Title
Energy Conversion and Management
Journal Volume
48
Journal Issue
3
Journal Page Range
p. 764-777
ISSN
0196-8904
CODEN
ECMADL

INIS

Country of Publication
United Kingdom
Country of Input or Organization
International Atomic Energy Agency (IAEA)
INIS RN
39012126
Subject category
S29: ENERGY PLANNING, POLICY AND ECONOMY;
Descriptors DEI
AIR; DETECTION; OPERATION; SENSORS; TURBINES
Descriptors DEC
EQUIPMENT; FLUIDS; GASES; MACHINERY; TURBOMACHINERY

Optional Information

Copyright
Copyright (c) 2006 Elsevier Science B.V., Amsterdam, The Netherlands, All rights reserved.