Published 1983 | Version v1
Journal article

Operation of the motors and capacitors in separate network at Eurodif plant

Description

The very high MVA installed capacity of the motors, capacitors and cables at the uranium enrichment plant at Tricastin required extensive investigations and experiments to avoid accidental phenomena of self-excitation that might cause overvoltages dangerous to equipment. An order of magnitude of the results from computation and from tests is given and the significance of taking into account, in calculations, the phenomena of saturation of the transformers is emphasized

Abstract (French)

L'importance de la puissance installee en moteurs, condensateurs et cables a l'usine d'enrichissement de l'uranium du Tricastin a necessite des etudes et experimentations approfondies pour eviter les phenomenes accidentels d'auto-excitation pouvant entrainer des surtensions dangereuses pour les materiels. On donne les ordres de grandeur des resultats de calcul et d'essais et on souligne l'importance de la prise en compte dans les calculs des phenomenes de saturation des transformateurs

Additional details

Additional titles

Original title (French)
Fonctionnement des moteurs et condensateurs en reseau separe a l'usine d'Eurodif

Publishing Information

Journal Title
Rev. Gen. Electr.
Journal Issue
no.2
Series
Rev. Gen. Electr.
ISSN
0035-3116