Performance of the two Point Lepreau GS standby generators during the first three years of licensed station operation is reviewed. It is shown that the mandated reliability/availability requirements have been met. The nature of starting and running failures has been examined and the consequences, in terms of design and procedural changes, discussed. A brief review of standby generator outages is included to permit estimates of standby generator availability and total Class III standby power unavailability. A pair of simple equations is introduced as a means of estimating the probable economic penalty, both cumulative and incremental, associated with the running failure of one standby generator while the other is on a maintenance outage. (authors)

Files

47076526.pdf

Files (505.1 kB)

Name Size Download all
md5:4a1f1040eb7482655251702d735fd008
505.1 kB Preview Download
Part of:
Operating experience relating to on-site electric power sources. Proceedings of a Specialist Meeting

Additional details

Publishing Information

Imprint Title
Operating experience relating to on-site electric power sources. Proceedings of a Specialist Meeting
Imprint Pagination
399 p.
Journal Page Range
p. 249-262
Report number
NEA-CSNI-R--1986-115

Conference

Title
CSNI specialist meeting on operating experience relating to on-site electric power sources
Dates
16-18 Oct 1985
Place
London (United Kingdom)

Optional Information

Notes
1 ref.