Published May 17, 2002 | Version v1
Miscellaneous

A computer simulation appraisal of non-residential low energy cooling systems in California

Description

An appraisal of the potential performance of different Low Energy Cooling (LEC) systems in nonresidential buildings in California is being conducted using computer simulation. The paper presents results from the first phase of the study, which addressed the systems that can be modeled, with the DOE-2.1E simulation program. The following LEC technologies were simulated as variants of a conventional variable-air-volume system with vapor compression cooling and mixing ventilation in the occupied spaces: Air-side indirect and indirect/direct evaporative pre-cooling. Cool beams. Displacement ventilation. Results are presented for four populous climates, represented by Oakland, Sacramento, Pasadena and San Diego. The greatest energy savings are obtained from a combination of displacement ventilation and air-side indirect/direct evaporative pre-cooling. Cool beam systems have the lowest peak demand but do not reduce energy consumption significantly because the reduction in fan energy is offse t by a reduction in air-side free cooling. Overall, the results indicate significant opportunities for LEC technologies to reduce energy consumption and demand in nonresidential new construction and retrofit

Availability note (English)

Available from OSTI as DE00799624; www.osti.gov/servlets/purl/799624-xpGrF4/native/

Additional details

Publishing Information

Imprint Pagination
[vp.]
Report number
LBNL--50677

INIS

Country of Publication
United States
Country of Input or Organization
United States
INIS RN
33066969
Subject category
S29: ENERGY PLANNING, POLICY AND ECONOMY;
Resource subtype / Literary indicator
Non-conventional Literature
Descriptors DEI
BLOWERS; COMPUTERS; COOLING SYSTEMS; ENERGY CONSUMPTION; ENERGY EFFICIENCY; PERFORMANCE; SIMULATION; VENTILATION
Descriptors DEC
EFFICIENCY; ENERGY SYSTEMS