Published January 2021 | Version v1
Journal article

Preventing cascading failure of electric power protection systems in nuclear power plant

  • 1. KEPCO International Nuclear Graduate School, Ulsan (Korea, Republic of)

Description

Cascading failure is the main cause of large blackouts in electrical power systems; this paper analyzes a cascading failure in Hanbit nuclear power plant unit two (2) caused by a circuit breaker (CB) operation failure. This malfunction has been expanded to the loss of offsite power (LOOP). In this study, current practices are reviewed and then the methodologies of how to prevent cascading failures in protection power systems are introduced. An overview on the implementation of IEC61850 GOOSE messaging-based zone selective interlocking (ZSI) scheme as key solution is proposed. In consideration of ZSI blocking time, all influencing factors such as circuit breaker opening time, relay I/O response time and messages travelling time in the communication network should be taken into account. The purpose of this paper is to elaborate on the effect of cascading failure in NPP electrical power protection system and propose preventive actions for this failures. Finally, the expected advantages and challenges are elaborated

Additional details

Publishing Information

Journal Title
Nuclear Engineering and Technology
Journal Volume
53
Journal Issue
1
Series
19 refs, 8 figs, 4 tabs
Journal Page Range
p. 121-130
ISSN
1738-5733