Multi-compartment Fire Modeling for Switchgear Room using CFAST
Creators
- 1. Korea Atomic Energy Research Institute, Daejeon (Korea, Republic of)
Description
In this study, multi-compartment fire modeling for fire propagation scenario from SWGR A to SWGR B is performed using CFAST. New fire PSA method (NUREG/CR-6850) requires that the severity factor is to be calculated by fire modeling. If fire modeling is not performed, the severity factor should be estimated as one conservatively. Also, the possibility of the damages of components and cables located at adjacent compartments should be considered. Detailed fire modeling of multi-compartment fires refers to the evaluation of fire-generated conditions in one compartment that spread to adjacent ones. In general, the severity factor for multi-compartment fire scenario is smaller than that of single compartment scenario. Preliminary quantification of Hanul Unit 3 fire PSA was performed without fire modeling. As a result of quantification, multi-compartment scenario, fire propagation scenario from switchgear room (SWGR) A to SWGR B, is one of significant contributor to the CDF. In this study, fire modeling of multi-compartment was performed by Consolidated Fire Growth and Smoke Transport (CFAST) to identify the possibility of fire propagation. As a result of fire simulation, it is identified that fire propagation has little influences
Additional details
Publishing Information
- Publisher
- KNS
- Imprint Place
- Daejeon (Korea, Republic of)
- Imprint Title
- Proceedings of the KNS 2015 Fall Meeting
- Imprint Pagination
- [1 CD-ROM]
- Journal Page Range
- [3 p.]
Conference
- Title
- 2015 Fall meeting of the KNS
- Dates
- 28-30 Oct 2015
- Place
- Kyungju (Korea, Republic of)
INIS
- Country of Publication
- Korea, Republic of
- Country of Input or Organization
- Korea, Republic of
- INIS RN
- 47085286
- Subject category
- S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Resource subtype / Literary indicator
- Conference, Non-conventional Literature
- Descriptors DEI
- COMPUTER CALCULATIONS; DAMAGE; FIRES; PROBABILITY; SAFETY ANALYSIS; SIMULATION
Optional Information
- Notes
- 5 refs, 3 figs, 1 tab