Published October 2015 | Version v1
Miscellaneous

Multi-compartment Fire Modeling for Switchgear Room using CFAST

  • 1. Korea Atomic Energy Research Institute, Daejeon (Korea, Republic of)

Description

In this study, multi-compartment fire modeling for fire propagation scenario from SWGR A to SWGR B is performed using CFAST. New fire PSA method (NUREG/CR-6850) requires that the severity factor is to be calculated by fire modeling. If fire modeling is not performed, the severity factor should be estimated as one conservatively. Also, the possibility of the damages of components and cables located at adjacent compartments should be considered. Detailed fire modeling of multi-compartment fires refers to the evaluation of fire-generated conditions in one compartment that spread to adjacent ones. In general, the severity factor for multi-compartment fire scenario is smaller than that of single compartment scenario. Preliminary quantification of Hanul Unit 3 fire PSA was performed without fire modeling. As a result of quantification, multi-compartment scenario, fire propagation scenario from switchgear room (SWGR) A to SWGR B, is one of significant contributor to the CDF. In this study, fire modeling of multi-compartment was performed by Consolidated Fire Growth and Smoke Transport (CFAST) to identify the possibility of fire propagation. As a result of fire simulation, it is identified that fire propagation has little influences

Part of:
Proceedings of the KNS 2015 Fall Meeting

Additional details

Publishing Information

Publisher
KNS
Imprint Place
Daejeon (Korea, Republic of)
Imprint Title
Proceedings of the KNS 2015 Fall Meeting
Imprint Pagination
[1 CD-ROM]
Journal Page Range
[3 p.]

Conference

Title
2015 Fall meeting of the KNS
Dates
28-30 Oct 2015
Place
Kyungju (Korea, Republic of)

INIS

Country of Publication
Korea, Republic of
Country of Input or Organization
Korea, Republic of
INIS RN
47085286
Subject category
S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
Resource subtype / Literary indicator
Conference, Non-conventional Literature
Descriptors DEI
COMPUTER CALCULATIONS; DAMAGE; FIRES; PROBABILITY; SAFETY ANALYSIS; SIMULATION

Optional Information

Notes
5 refs, 3 figs, 1 tab