Published May 1985
| Version v1
Report
Restricted
Demonstration of containment purge and vent valve operability for the Hope Creek Generating Station, Unit 1 (Docket No. 50-354)
Description
The containment purge and vent valve qualification program for the Hope Creek Generating Station has been reviewed by the NRC Licensing Support Section. The review indicates that the licensee has demonstrated the dependability of containment isolation against the buildup of containment pressure due to a LOCA/DBA with the restrictions that during operating conditions 1, 2, and 3 all purge and vent valves will be sealed closed and under administrative control, and during power ascension and descension conditions the 26 in. inboard valve (1-GS-HV-4952) will be used in series with the 2 in. bypass valve (1-GS-HV-4951) to control the release of containment pressure
Availability note (English)
MF available from INIS under the Report Number; Available from NTIS, PC A02/MF A01 - GPO as TI85014636.
Files
Additional details
Publishing Information
- Imprint Pagination
- 13 p.
- Report number
- EGG-EA--6861
INIS
- Country of Publication
- United States
- Country of Input or Organization
- United States
- INIS RN
- 17013270
- Subject category
- S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Descriptors DEI
- CONTAINMENT; DESIGN BASIS ACCIDENTS; HOPE CREEK-1 REACTOR; LOSS OF COOLANT; VALVES; VENTS
- Descriptors DEC
- ACCIDENTS; BWR TYPE REACTORS; CONTROL EQUIPMENT; ENRICHED URANIUM REACTORS; EQUIPMENT; FLOW REGULATORS; POWER REACTORS; REACTOR ACCIDENTS; REACTORS; THERMAL REACTORS; WATER COOLED REACTORS; WATER MODERATED REACTORS