Published April 2016 | Version v1
Book

The modification method of periodic test of emergency diesel generator in fangjiashan nuclear power plant

Creators

  • 1. CNNC Nuclear Power Operations Management Co., Ltd., Jiaxing (China)

Description

The periodic load testing method of the emergency diesel generator of M310 nuclear power plant is introduced, and its problems are analyzed. According to standard IEEE387, a modified method is put forward, which allows the emergency diesel generator connected to the grid to perform the periodic load test. The modified method which is feasible or not depends on the short-circuit current of the medium voltage electrical system during the test. That is to say the short-circuit current must not exceed the breaking capacity of the circuit break. The calculation results show that the three-phase short-circuit current of the medium voltage electrical system is not over the limitation, therefore the modified method meets the relevant standards requirements. (author)

Part of:
Progress report on nuclear science and technology in China (Vol.4). Proceedings of academic annual meeting of China Nuclear Society in 2015, No.2--nuclear energy & power sub-volume

Additional details

Publishing Information

Publisher
Atomic Energy Press
Imprint Place
Beijing (China)
ISBN
978-7-5022-7103-9
Imprint Title
Progress report on nuclear science and technology in China (Vol.4). Proceedings of academic annual meeting of China Nuclear Society in 2015, No.2--nuclear energy & power sub-volume
Imprint Pagination
377 p.
Journal Page Range
p. 106-111

Conference

Title
2015 academic annual meeting of China Nuclear Society
Dates
21-24 Sep 2015
Place
Mianyang (China)

Optional Information

Notes
1 fig., 1 tab., 8 refs.