Published September 2006 | Version v1
Journal article

Research on a compact adsorption room air conditioner

  • 1. Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, 1954 Huashan Road, Shanghai 200030 (China)
  • 2. Panasonic R and D Center, Suzhou Co., Ltd., Suzhou 215000 (China)

Description

A novel compact adsorption room air conditioner with a cooling capacity of 1 kW has been designed, and two prototypes have been built. A two bed, continuous adsorption refrigeration cycle with heat recovery and mass recovery is adopted. Micropore spherical silica gel and water are selected as the working pair. A gravity heat pipe with methanol as working medium is designed to output the cooling. Experimental investigations have indicated that under typical air conditioning conditions, for the first prototype, a cooling capacity of 687 W and a COP (coefficient of performance) of 0.307 can be obtained. However, for the improved one, a cooling capacity of 790 W and a COP of 0.446 can be reached. It is also proved that the operating temperatures have strong influences on the performance. The designed room air conditioner can be driven by a low grade heat source (<90 oC) and has small dimensions of 300 mm (depth), 500 mm (width) and 950 mm (height)

Additional details

Identifiers

DOI
10.1016/j.enconman.2005.12.005;
PII
S0196-8904(05)00338-9;

Publishing Information

Journal Title
Energy Conversion and Management
Journal Volume
47
Journal Issue
15-16
Journal Page Range
p. 2167-2177
ISSN
0196-8904
CODEN
ECMADL

Optional Information

Copyright
Copyright (c) 2006 Elsevier Science B.V., Amsterdam, The Netherlands, All rights reserved.