The effectiveness of using the calculated braking current for longitudinal differential protection of 110 – 750 kV shunt reactors
Creators
- 1. JSC "E and E" (Russian Federation)
- 2. LLC Selekt Co. (Russian Federation)
Description
The use of the function of effective current braking of the longitudinal differential protection of shunt reactors to offset current surges, which enables the sensitivity of differential protection to be increased when there are short circuits with low damage currents, is considered. It is shown that the use of the calculated braking characteristic enables the reliability of offset protection from transients to be increased when the reactor is connected, which is accompanied by the flow of asymmetric currents containing an aperiodic component.
Additional details
Identifiers
Publishing Information
- Journal Title
- Power Technology and Engineering (Print)
- Journal Volume
- 47
- Journal Issue
- 1
- Journal Page Range
- p. 76-82
- ISSN
- 1570-145X
INIS
- Country of Publication
- United States
- Country of Input or Organization
- International Atomic Energy Agency (IAEA)
- INIS RN
- 44081575
- Subject category
- S42: ENGINEERING; S24: POWER TRANSMISSION AND DISTRIBUTION;
- Descriptors DEI
- DAMAGE; ELECTRIC CURRENTS; ELECTRICAL FAULTS; ELECTRICAL TRANSIENTS; RELIABILITY; SAFETY; SHUNT REACTORS; SURGES
- Descriptors DEC
- CURRENTS; ELECTRICAL EQUIPMENT; EQUIPMENT; TRANSIENTS; VOLTAGE DROP
Optional Information
- Copyright
- Copyright (c) 2013 Springer Science+Business Media New York
- Notes