Published May 2013 | Version v1
Journal article

The effectiveness of using the calculated braking current for longitudinal differential protection of 110 – 750 kV shunt reactors

  • 1. JSC "E and E" (Russian Federation)
  • 2. LLC Selekt Co. (Russian Federation)

Description

The use of the function of effective current braking of the longitudinal differential protection of shunt reactors to offset current surges, which enables the sensitivity of differential protection to be increased when there are short circuits with low damage currents, is considered. It is shown that the use of the calculated braking characteristic enables the reliability of offset protection from transients to be increased when the reactor is connected, which is accompanied by the flow of asymmetric currents containing an aperiodic component.

Additional details

Identifiers

Publishing Information

Journal Title
Power Technology and Engineering (Print)
Journal Volume
47
Journal Issue
1
Journal Page Range
p. 76-82
ISSN
1570-145X

INIS

Country of Publication
United States
Country of Input or Organization
International Atomic Energy Agency (IAEA)
INIS RN
44081575
Subject category
S42: ENGINEERING; S24: POWER TRANSMISSION AND DISTRIBUTION;
Descriptors DEI
DAMAGE; ELECTRIC CURRENTS; ELECTRICAL FAULTS; ELECTRICAL TRANSIENTS; RELIABILITY; SAFETY; SHUNT REACTORS; SURGES
Descriptors DEC
CURRENTS; ELECTRICAL EQUIPMENT; EQUIPMENT; TRANSIENTS; VOLTAGE DROP

Optional Information

Copyright
Copyright (c) 2013 Springer Science+Business Media New York
Notes
http://www.springer-ny.com