Published November 26, 2009 | Version v1
Journal article

Control and Data Acquisition System for KSTAR ICRF

  • 1. Korea Atomic Energy Research Institute, 150 Dukjin, Daejeon 305-353 (Korea, Republic of)

Description

An ICRF discharge cleaning and a plasma heating experiment were performed in KSTAR toka-mak. For an automated operation and the diagnostics of the ICRF system, the ICRF local network was designed and implemented. This internal network provides monitoring, RF protection, remote control and RF diagnostics. All the functions of the control system were realized by customized DSP units. The DSP units were tied by a local network in parallel. For RF diagnostics, a detector based on digital I/Q demodulation technique was fabricated. The I/Q detector collects the RF amplitude and phase at the same time without errors from I/Q imbalance inherent in an analog counterpart. During the first experimental campaign of the KSTAR tokamak, the control system was operated as expected without any major problems such as affecting the tokamak operation. The transmitter was protected from the harmful over-voltage events through a reliable operation of the system. Details of ICRF control system and RF detecting technique with a brief experimental result will be presented.

Additional details

Identifiers

Publishing Information

Journal Title
AIP Conference Proceedings
Journal Volume
1187
Journal Issue
1
Journal Page Range
p. 313-316
ISSN
0094-243X
CODEN
APCPCS

Conference

Title
18. topical conference on radio frequency power in plasmas
Dates
24-26 Jun 2009
Place
Gent (Belgium)

Optional Information

Notes
(c) 2009 American Institute of Physics