Forsmark Unit 3, Sweden, 2013. Annex III. Description of Selected Open Phase Events
Creators
Description
On 30 May 2013, during a refuelling outage, a combination of human error and a loose cable connection resulted in a double OPC in the 400 kV breaker. The failure was not detected by the loss of voltage relays and, as a result, the standby AC power sources did not start (no degraded voltage relays implemented).
Additional details
Identifiers
Publishing Information
- Publisher
- IAEA
- Imprint Place
- Vienna (International Atomic Energy Agency (IAEA))
- ISBN
- 978-92-0-108516-0
- Imprint Title
- Impact of Open Phase Conditions on Electrical Power Systems of Nuclear Power Plants
- Imprint Pagination
- 104 p.
- Journal Issue
- no. 91
- Series
- Safety Reports Series
- Journal Page Range
- p. 72-73
- ISSN
- 1020-6450
INIS
- Country of Publication
- International Atomic Energy Agency (IAEA)
- Country of Input or Organization
- International Atomic Energy Agency (IAEA)
- INIS RN
- 49074775
- Subject category
- S22: GENERAL STUDIES OF NUCLEAR REACTORS; S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Descriptors DEI
- CABLES; CIRCUIT BREAKERS; ELECTRIC POTENTIAL; ERRORS; FAILURES; FORSMARK-3 REACTOR; HUMAN FACTORS; JOINTS; OUTAGES; RELAYS; VOLTAGE DROP
- Descriptors DEC
- BWR TYPE REACTORS; ELECTRICAL EQUIPMENT; ENRICHED URANIUM REACTORS; EQUIPMENT; EQUIPMENT PROTECTION DEVICES; POWER REACTORS; REACTORS; THERMAL REACTORS; WATER COOLED REACTORS; WATER MODERATED REACTORS
Optional Information
- Notes
- This record replaces 48012263
- Secondary number(s)
- STI/PUB--1755