The considerations to use soft start AC controllers in nuclear application

  • 1. Atomic Energy of Canada Limited, Mississauga, Ontario (Canada)

Description

Motors larger than 200 HP shall be fed from 4.16 kV or 2.4 kV fused starters. In CANDU reactors all large pumps motors are supplied directly from the 13.8 kV, 6.3 kV or 4.16 kV AC system. In the MAPLE reactors, the Primary Coolant System pumps are supplied directly from the 2.4 kV AC system. Starting and stopping a pump may be easy, but the consequences may not always be ones we wanted. It can result in high start current that require large cables and fuses, or hydraulic shocks known as 'water hammer' can cause stress and damage to pipes, valves, gaskets and seals. If the nuclear plant installs soft starters, the result will be pump protection, which provides start and stop control, preventing both water hammer and expensive high start currents. (author)

Part of:
New nuclear frontiers. 30th annual Canadian Nuclear Society conference and 33rd CNS/CNA student conference

Additional details

Publishing Information

Publisher
Canadian Nuclear Society
Imprint Place
Toronto, Ontario (Canada)
ISBN
0-919784-95-X
Imprint Title
New nuclear frontiers. 30th annual Canadian Nuclear Society conference and 33rd CNS/CNA student conference
Imprint Pagination
275 Megabytes
Journal Page Range
[9 p.]

Conference

Title
30. annual canadian nuclear society conference; 33. CNS/CNA student conference
Dates
31 May - 3 Jun 2009
Place
Calgary, Alberta (Canada)

Optional Information

Notes
4 refs., 1 tab., 11 figs.