Published March 2015 | Version v1
Journal article

Study on control method of the actuators accepting commands from different classifications in nuclear power plant

  • 1. Eletric and I and C Institute, China Nuclear Power Engineering Co., Ltd., Beijing (China)
  • 2. Nuclear and Radiation Safety Center, MEP, Beijing (China)

Description

The distributed control system has become the main control system for the nuclear power plant, consisting of 1E and non-1E parts. Because the safety actuators accept commands from different safety classifications, this is a difficulty of controlling those actuators in nuclear power plant. This article discusses about the control method for safety actuators accepting commands from different classifications. Firstly, one control method adopted in new nuclear power projects is introduced. Then based on this, an optimized method is raised. The new method mainly concludes two points than the adopted method: 1. The concept 'local control mode' is introduced into the signal priority logic modules, and the priority logic module turns into local mode for the non-1E control system once it accepts safety signal; 2. The 'remote control mode' is added into the module of the safety actuator in the non-1E control system, and this can make the non-1E control system abandon controlling the safety actuator when the relevant priority logic module accept the safety signal. Based on verifying the correctness of modified scheme, comparisons between the fore-and-aft schemes are provided to summary the merits of the optimized method. It is concluded that optimized scheme is better in the aspects of reliability, safety and economy. (authors)

Additional details

Publishing Information

Journal Title
Chinese Journal of Nuclear Science and Engineering
Journal Volume
35
Journal Issue
1
Journal Page Range
p. 136-140
ISSN
0258-0918

Optional Information

Notes
2 figs., 2 tabs., 6 refs.