Study on eliminating fire dampers to maintain process confinement

Description

The DOE General Design Criteria for the Defense Waste Processing Facility (DWPF) at the Westinghouse Savannah River Site (WSRS) requires the NFPA National Fire Codes to be incorporated into the design and simultaneously maintain process confinement integrity to prevent the release of radioactivity. Although the NFPA Standard for the Installation of Air Conditioning and Ventilation Systems, NFPA 90, requires fire dampers (FD) in HVAC duct penetrations of two hour rated fire barriers, closure of fire dampers at DWPF may compromise the integrity of the process confinement system. This leads to the need for an overall risk assessment to determine the value of 39 fire dampers that are identified later in the study as capable of a confinement system upset

Availability note (English)

MF available from INIS under the Report Number; OSTI as DE92014587; NTIS; INIS; US Govt. Printing Office Dep.

Files

Restricted

The record is publicly accessible, but files are restricted to users with access.

Additional details

Publishing Information

Imprint Pagination
29 p.
Report number
WSRC-MS--91-294

Conference

Title
Winter meeting of the American Nuclear Society (ANS).
Dates
10-15 Nov 1991.
Place
San Francisco, CA (United States).

Optional Information

Contract/Grant/Project number
Contract AC09-89SR18035
Funding organization
USDOE, Washington, DC (United States).
Secondary number(s)