Measured energy savings and demand reduction from a reflective roof membrane on a large retail store in Austin; FINAL

Description

In this study, we measured and documented summertime air-conditioning (a/c) daily energy savings and demand reduction from a reflective roof membrane retrofit on a large retail store in Austin, Texas. The original black rubber membrane was replaced with white thermoplastic resulting in a decrease in the average maximum roof surface temperature from 168 degrees F (76 degrees C) to 126 degrees F (52 degrees C). This building, with 100,000ft2 (9300m2) of roof area, yielded 3.6Wh/ft2 (39Wh/m2) in a/c average daily energy savings and 0.35W/ft2 (3.8W/m2) in average reduced demand. Total a/c annual abated energy and demand expenditures were estimated to be$7200 or$0.072/ft2 ($0.77/m2). Based on cost data provided by the building manager, the payback is instantaneous with negligible incremental combined labor and material costs. The estimated present value of future abated expenditures ranged from$62,000 to$71,000 over the baseline 13-year service life of the roof membrane

Availability note (English)

Available from OSTI as DE00787107

Additional details

Publishing Information

Imprint Pagination
[vp.]
Report number
LBNL--47149

INIS

Country of Publication
United States
Country of Input or Organization
United States
INIS RN
33055456
Subject category
S29: ENERGY PLANNING, POLICY AND ECONOMY;
Resource subtype / Literary indicator
Non-conventional Literature
Descriptors DEI
AIR CONDITIONING; ECONOMICS; MEMBRANES; POWER DEMAND; ROOFS; RUBBERS; SERVICE LIFE; SUPPLY AND DEMAND; THERMOPLASTICS
Descriptors DEC
DEMAND; ELASTOMERS; LIFETIME; MATERIALS; MECHANICAL STRUCTURES; ORGANIC COMPOUNDS; ORGANIC POLYMERS; PETROCHEMICALS; PETROLEUM PRODUCTS; PLASTICS; POLYMERS; SYNTHETIC MATERIALS