Estimation of relay screening criteria for the NPP seismic probabilistic risk assessment
Description
A relay may be screened out in SPRA if the relay chatter capacity is shown to be sufficiently high based upon preliminary bounding calculation. For screened out relays, no further detailed fragility analysis would be performed. Seismic capacity of relay is conservatively estimated based on the dynamic qualification data, fragility data or earthquake experience data. The fragility test data is required for the ultimate seismic capacity of relay. It is very difficult to estimate the fragility level of relays, since the fragility data for relay is rare. In past SPRAs, the relay chatter screening has been performed based on the review level earthquake used in seismic margin analysis (SMA). To account for the capacity level assumed in the screening level an additional element or surrogate element must be added to the SPRA to represent the screened out component. The state-of-the-art review and estimation of relay screening criteria were performed to proposed the realistic screening criteria and the procedures for considering the screened out element
Additional details
Publishing Information
- Publisher
- KNS
- Imprint Place
- Taejon (Korea, Republic of)
- Imprint Title
- Proceedings of the Korean Nuclear Society autumn meeting
- Imprint Pagination
- [CD-ROM]
- Journal Page Range
- [10 p.]
Conference
- Title
- 2001 autumn meeting of the Korean Nuclear Society
- Dates
- 24-26 Oct 2001
- Place
- Seoul (Korea, Republic of)
INIS
- Country of Publication
- Korea, Republic of
- Country of Input or Organization
- Korea, Republic of
- INIS RN
- 33065699
- Subject category
- S22: GENERAL STUDIES OF NUCLEAR REACTORS; S58: GEOSCIENCES;
- Resource subtype / Literary indicator
- Conference, Non-conventional Literature
- Descriptors DEI
- EARTHQUAKES; NUCLEAR POWER PLANTS; PROBABILISTIC ESTIMATION; RELAYS; RISK ASSESSMENT; SEISMIC EFFECTS
- Descriptors DEC
- ELECTRICAL EQUIPMENT; EQUIPMENT; NUCLEAR FACILITIES; POWER PLANTS; SEISMIC EVENTS; THERMAL POWER PLANTS
Optional Information
- Notes
- 13 refs, 1 fig, 2 tabs