Description

This paper reports that deterioration in the insulation performance of extra-high voltage XLPE cables is believed to be attributable to the deterioration caused by partial discharges. In the authors study, after using an XLPE cable to investigate the behavior of partial discharges under various adverse conditions, we succeeded in developing a highly sensitive new method of measuring partial discharge in XLPE cable lines. Partial discharges in a 275 kV XLPE cable live line has been measured using this newly developed method. As a result, a detection sensitivity of 1 pC has been achieved