Published February 1983 | Version v1
Report

Reliability of the emergency AC power system at nuclear power plants

  • 1. Oak Ridge National Lab., TN

Description

The reliability of the emergency ac power systems typical of most nuclear power plants was estimated, and the cost and increase in reliability for several improvements were estimated. Fault trees were constructed based on a detailed design review of the emergency ac power systems of 18 nuclear plants. The failure probabilities used in the fault trees were calculated from extensive historical data collected from Licensee Event Reports (LERs) and from operating experience information obtained from nuclear plant licensees. No one or two improvements can be made at all plants to significantly increase the industry-average emergency ac power system reliability; rather the most beneficial improvements are varied and plant specific. Improvements in reliability and the associated costs are estimated using plant specific designs and failure probabilities

Additional details

Additional titles

Augmented title (English)
PWR; BWR

Publishing Information

Imprint Title
Proceedings of the international meeting on thermal nuclear reactor safety. Vol. 1
Journal Page Range
p. 479-488.
Report number
NUREG/CP--0027-Vol.1

Conference

Title
International meeting on thermal nuclear reactor safety (ANS topical meeting).
Dates
29 Aug - 2 Sep 1982.
Place
Chicago, IL (USA).