Reliability of the emergency AC power system at nuclear power plants
Description
The reliability of the emergency ac power systems typical of most nuclear power plants was estimated, and the cost and increase in reliability for several improvements were estimated. Fault trees were constructed based on a detailed design review of the emergency ac power systems of 18 nuclear plants. The failure probabilities used in the fault trees were calculated from extensive historical data collected from Licensee Event Reports (LERs) and from operating experience information obtained from nuclear plant licensees. No one or two improvements can be made at all plants to significantly increase the industry-average emergency ac power system reliability; rather the most beneficial improvements are varied and plant specific. Improvements in reliability and the associated costs are estimated using plant specific designs and failure probabilities
Additional details
Additional titles
- Augmented title (English)
- PWR; BWR
Publishing Information
- Imprint Title
- Proceedings of the international meeting on thermal nuclear reactor safety. Vol. 1
- Journal Page Range
- p. 479-488.
- Report number
- NUREG/CP--0027-Vol.1
Conference
- Title
- International meeting on thermal nuclear reactor safety (ANS topical meeting).
- Dates
- 29 Aug - 2 Sep 1982.
- Place
- Chicago, IL (USA).
INIS
- Country of Publication
- United States
- Country of Input or Organization
- United States
- INIS RN
- 14792367
- Subject category
- S61: RADIATION PROTECTION AND DOSIMETRY; S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS; S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Resource subtype / Literary indicator
- Conference
- Descriptors DEI
- BWR TYPE REACTORS; FAILURES; FAULT TREE ANALYSIS; POWER SUPPLIES; PWR TYPE REACTORS; REACTOR SAFETY; RELIABILITY; SAFETY ENGINEERING
- Descriptors DEC
- ELECTRONIC EQUIPMENT; EQUIPMENT; REACTORS; SAFETY; SYSTEM FAILURE ANALYSIS; SYSTEMS ANALYSIS; WATER COOLED REACTORS; WATER MODERATED REACTORS