Probabilistic safety criteria used to evaluate loss of off-site power

  • 1. Institut Rudjer Boskovic, Zagreb (Yugoslavia)
  • 2. Republic Energy Inspectorate, Ljubljana (Yugoslavia)

Description

When the malfunctioning transformer T3 at Krsko NPP caused the loss of second independent off-site power source, the plant's Technical Specification required its repairment in 72 hours or the plant would be brought to hot shutdown (cold shutdown after 108 hours). Because it was not possible to repair the transformer on time, the Krsko NPP asked for the temporary change of Technical Specification based on several improvements which could be accomplished in a fairly short time period. The probabilistic study was performed to calculate relative effectiveness of the improvements. (author). 5 figs, 3 tabs

Part of:
Probabilistic safety criteria at the safety function/system level

Additional details

Publishing Information

Imprint Title
Probabilistic safety criteria at the safety function/system level
Imprint Pagination
108 p.
Journal Page Range
p. 83-94.
Report number
IAEA-TECDOC--523

Conference

Title
Technical committee meeting on probabilistic safety criteria at the safety function/system level.
Dates
26-30 Jan 1987.
Place
Vienna (Austria).

INIS

Country of Publication
International Atomic Energy Agency (IAEA)
Country of Input or Organization
International Atomic Energy Agency (IAEA)
INIS RN
21020291
Subject category
S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
Resource subtype / Literary indicator
Conference
Descriptors DEI
FAILURE MODE ANALYSIS; KRSKO REACTOR; OUTAGES; POWER SYSTEMS; PROBABILISTIC ESTIMATION; REACTOR SAFETY; SAFETY ANALYSIS
Descriptors DEC
ENRICHED URANIUM REACTORS; POWER REACTORS; PWR TYPE REACTORS; REACTORS; SAFETY; SYSTEM FAILURE ANALYSIS; SYSTEMS ANALYSIS; THERMAL REACTORS; WATER COOLED REACTORS; WATER MODERATED REACTORS

Optional Information