Published August 2003 | Version v1
Journal article

Two-phase flow distribution and phase separation through both horizontal and vertical branches

  • 1. Sungkyunkwan Univ., Suwon (Korea, Republic of)

Description

The present study investigated two-phase flow distribution and phase separation of R-22 refrigerant through various types of branch tubes. The key experimental parameters were the orientation of inlet and branch tubes (horizontal and vertical), diameter ratio of branch tube to inlet tube (1 and 0.61), mass flux (200-500kg/m2s), and inlet quality (0.1-0.4). The predicted local pressure profile in the tube with junction was compared and generally agreed with the measured data. The local pressure profile within the pressure recovery region after the junction has to be carefully investigated for modeling the pressure drop through the branch. The equal flow distribution case can be found by adjusting the orientation of the inlet and branch tubes and the diameter ratio of the branch tube to the inlet tube. The T-junction with horizontal inlet and branch tubes showed the nearly equal phase distribution ratio. The quality at the branch tube varied from 0 to 1 as the orientation of the branch tube changed, while it varied within ±50% as the orientation of the inlet tube changed

Additional details

Publishing Information

Journal Title
KSME International Journal
Journal Volume
17
Journal Issue
8
Series
19 refs, 7 figs, 1 tab
Journal Page Range
p. 1211-1218
ISSN
1226-4865

INIS

Country of Publication
Korea, Republic of
Country of Input or Organization
Korea, Republic of
INIS RN
36106171
Subject category
S42: ENGINEERING;
Descriptors DEI
AIR CONDITIONERS; HEAT EXCHANGERS; MIXTURES; PRESSURE DROP; REFRIGERANTS; TUBES; TWO-PHASE FLOW
Descriptors DEC
DISPERSIONS; FLUID FLOW; FLUIDS; WORKING FLUIDS