Electro magnetic compatibility testing verification and analysis of AP1000 nuclear power plants' uninterrupted power supply system
Creators
- 1. Shanghai Nuclear Engineering Research and Design Institute Co., Ltd., Shanghai (China)
- 2. Nuclear and Radiation Safety Center, Beijing (China)
Description
AP1000 use the fully digital instrument and control system. The digital instrument and control system are more easily affected by electromagnetic interference. So AP1000 put forward higher requirement for power system. This paper introduces the main reference standard of the electromagnetic compatibility (EMC) test of the uninterruptible power supply equipment (UPS). Take charger for example, the electromagnetic compatibility design has been verified, and the results are analyzed from CE101, CE102, RE102. The result indicate that 1E charger meet the requirement of AP1000 EMC test. put forward the reasonable solution for UPS conducted emissions too high, for subsequent electromagnetic compatibility design optimization of UPS provided empirical data support. (authors)
Additional details
Publishing Information
- Journal Title
- Chinese Journal of Nuclear Science and Engineering
- Journal Volume
- 40
- Journal Issue
- 1
- Journal Page Range
- p. 105-112
- ISSN
- 0258-0918
INIS
- Country of Publication
- China
- Country of Input or Organization
- China
- INIS RN
- 55067869
- Subject category
- S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Descriptors DEI
- AVAILABILITY; COMPATIBILITY; CONTROL SYSTEMS; INTERFERENCE; NUCLEAR POWER PLANTS; OPTIMIZATION; PWR TYPE REACTORS; TESTING; UNINTERRUPTIBLE POWER SUPPLIES; VERIFICATION
- Descriptors DEC
- ELECTRONIC EQUIPMENT; ENRICHED URANIUM REACTORS; EQUIPMENT; NUCLEAR FACILITIES; POWER PLANTS; POWER REACTORS; POWER SUPPLIES; REACTORS; THERMAL POWER PLANTS; THERMAL REACTORS; WATER COOLED REACTORS; WATER MODERATED REACTORS
Optional Information
- Notes
- 4 figs., 5 tabs., 6 refs.