Published February 2020 | Version v1
Journal article

Electro magnetic compatibility testing verification and analysis of AP1000 nuclear power plants' uninterrupted power supply system

  • 1. Shanghai Nuclear Engineering Research and Design Institute Co., Ltd., Shanghai (China)
  • 2. Nuclear and Radiation Safety Center, Beijing (China)

Description

AP1000 use the fully digital instrument and control system. The digital instrument and control system are more easily affected by electromagnetic interference. So AP1000 put forward higher requirement for power system. This paper introduces the main reference standard of the electromagnetic compatibility (EMC) test of the uninterruptible power supply equipment (UPS). Take charger for example, the electromagnetic compatibility design has been verified, and the results are analyzed from CE101, CE102, RE102. The result indicate that 1E charger meet the requirement of AP1000 EMC test. put forward the reasonable solution for UPS conducted emissions too high, for subsequent electromagnetic compatibility design optimization of UPS provided empirical data support. (authors)

Additional details

Publishing Information

Journal Title
Chinese Journal of Nuclear Science and Engineering
Journal Volume
40
Journal Issue
1
Journal Page Range
p. 105-112
ISSN
0258-0918

Optional Information

Notes
4 figs., 5 tabs., 6 refs.