Published December 2013 | Version v1
Journal article

Performances of air source heat pump system for a kind of mal-defrost phenomenon appearing in moderate climate conditions

  • 1. Department of Building Environment and Facility Engineering, College of Architecture and Civil Engineering, Beijing University of Technology, No. 100 Pingleyuan, Chaoyang District, Beijing 100124 (China)

Description

Highlights: ► Mal-defrost performances of ASHP in moderate environment are investigated. ► The system COP decreases to 2.3 under environment temperature of 7.9 °C. ► The decrease of the ASHP heating capacity can get to 43.4%. ► The origins of this special mal-defrost phenomenon were discussed. ► Suggestions were proposed to modify the current defrosting control strategies. - Abstract: To quantify the performance drop of the air source heat pump (ASHP) system under a special kind of mal-defrost phenomenon appearing in moderate climate conditions, a field test was conducted for 8 days at the initial stage of a heating season in Beijing, China. The mal-defrost was found with the more than 60% frosted area of the outdoor heat exchanger after the system running 5 days. During this frosting period, the system COP was significantly degraded, only 2.3 under an environment temperature of 7.9 °C. Comparing the test data before and after frosting, it was found that the mal-defrost decreased the COP up to 40.4% and the heating capacity to 43.4%. Such low energy efficiency continued quite a long time until the defrost control was started up manually by the authors. After defrosting, the COP reclaimed to the normal level of 5.0. The origins of this special mal-defrost phenomenon were discussed. And some suggestions were proposed to modify the current defrosting control strategy, which were helpful to avoid the mal-defrost problem in the current ASHP system and therefore improve the system performances

Availability note (English)

Available from http://dx.doi.org/10.1016/j.apenergy.2012.12.054

Additional details

Identifiers

DOI
10.1016/j.apenergy.2012.12.054;
PII
S0306-2619(12)00945-2;

Publishing Information

Journal Title
Applied Energy
Journal Volume
112
Journal Page Range
p. 1138-1145
ISSN
0306-2619
CODEN
APENDX

INIS

Country of Publication
United Kingdom
Country of Input or Organization
International Atomic Energy Agency (IAEA)
INIS RN
46008212
Subject category
S29: ENERGY PLANNING, POLICY AND ECONOMY;
Descriptors DEI
AIR SOURCE HEAT PUMPS; CHINA; CLIMATES; CONTROL; DEFROSTING; ENERGY EFFICIENCY; FIELD TESTS; FROST; HEAT EXCHANGERS; HEATING
Descriptors DEC
ASIA; EFFICIENCY; HEAT PUMPS; ICE; TESTING

Optional Information

Copyright
Copyright (c) 2012 Elsevier Science B.V., Amsterdam, The Netherlands, All rights reserved.